Wall mounting
Fasten the Transceiver Unit to a wall with two M4 screws via the two elongated holes of the
mounting rail.
NOTICE
Sufficient carrying capacity of the wall is required.
If the wall does not have a sufficient load-bearing capacity, the device may fall and be
damaged.
Ensure that the wall can bear four times the total weight of the device, including fixing
accessories.
NOTICE
Fasteners
If you use anchors and screws other than those specified below for wall mounting, safe
mounting is not guaranteed. The device can fall and may be damaged.
Use only the anchors and screws specified in the following table.
Material
Concrete
Plasterboard, at least 13 mm thick
Metal, at least 2 mm thick
IFP V2, IFP V2 PRO
Operating Instructions, 08/2019, A5E46641410-AA
Installing and connecting the device
Hole diameter
Select according to the
specification of the
mounting elements used
3.4 Installing Transceiver Unit
Fastener
Anchor, ∅ 6 mm, 40 mm long
Screw, ∅ 4 mm, 40 mm long
Toggle plug, ∅ 12 mm, 50 mm long
Screw M4 × 15
M4 nut
57