Completing The Test - ABB REB 551-C3*2.5 Installation And Commissioning Manual

Breaker protection and control terminal
Table of Contents

Advertisement

8.5
Fuse failure supervision (FUSE)
4.
Apply normal conditions as in step 1.
The FUSE-VTSU, FUSE-VTSZ and FUSE-VTF3PH signals should re-
set, if activated. See step 3.
5.
Change the voltages and currents in all three phases simultanously.
The voltage change should be greater then set DU> and the current
change should be greater then the set DI<.
The FUSE-VTSU, FUSE-VTSZ and FUSE-VTF3PH signals should not
appear.
6.
Disconnect the dc voltage to the FUSE-CBCLOSED binary input.
7.
Apply normal conditions as in step 1.
8.
Repeat step 3.
9.
Connect the nominal voltages in all three phases and feed a current
below the operate level in all three phases.
10. Keep the current constant. Disconnect the voltage in all three phas-
es simultaneously.
The FUSE-VTSU, FUSE-VTSZ and FUSE-VTF3PH signals should not
appear.

Completing the test

Continue to test another function or complete the test by setting the test mode to off.