Overview

Overview
The customer specific values for each setting parameter and a configuration file has to be avail-
able before the terminal can be set and configured, if the terminal is not delivered with a config-
uration.
Use the CAP 531 configuration tool to verify if the terminal has the expected configuration. A
new configuration is performed with the CAP tool. The binary outputs can be selected from a
signal list where the signals are grouped under their function names. It is also possible to specify
a user-defined name for each input and output signal.
The configuration can be downloaded through the front connector on the local HMI or via the
rear SPA port.
Each function included in the terminal has several setting parameters which have to be set in or-
der to make the terminal behave as intended. A default value is provided for each parameter from
factory. A setting file can be prepared using the parameter setting tool (PST), which is available
in the CAP 540 package.
All settings can be:
Entered manually through the local HMI.
Downloaded from a PC, either locally or remotely using SMS/SCS. Front or rear
port communication has to be established before the settings can be downloaded.
Note!
Be sure to configure the functional input HMI--BLOCKSET to only one of the available binary
inputs before setting the parameter SettingRestrict to Block in the local HMI.
Setting and configuring the terminal