S4
Linefeed Character
Range
0 ... 127 decimal
Default
10 (Linefeed)
Register S4 defines the linefeed character.
S5
Backspace Character
Range
0 ... 32, 127 decimal
Default
8 (Backspace)
Register S5 defines the backspace character.
S30
Inactivity Timer
Range
0 ... 255 (from device software 14.x on)
Default
0 (timer off)
In register S30, you can set the time the modems waits before it kills the connection
automatically, if there has been no reception or transmission of data in the meantime. 0
deactivates the inactivity timer (Entry in seconds).
S31
Baudrate
Range
1 ... 7
Default
3 ( = 9600 baud)
In the S31 register, you can set the baud rate. The baud rate defines the number of state
changes of the transmitted signal per second.
1=2400
2=4800
S32
Parity
Range
0 ... 4
Default
0 ( no parity )
In the S32 register, you can set the parity bit
for error detection during asynchronous data transmission. Part of the data transmission
format. Occasionally no parity, constantly one (mark) or zero (space). Even parity means
that the bit is set, if the data bit number is even and vice versa for odd parity. 0=None
1=Even 2=Odd 3=Mark 4=Space
54 / 77
3=9600
4=19200
5=38400
6=57600
7XV5655-0BB00
7=115200
C53000-G1176-C175-2