Determining The Mains Choke; Dimensioning The Mains Contactor - Bosch Rexroth IndraDrive CsDrive System with HCS01 Project Planning Manual

Hide thumbs Also See for Rexroth IndraDrive CsDrive System with HCS01:
Table of Contents

Advertisement

102/341
Bosch Rexroth AG
Combining the individual components

Determining the Mains Choke

Dimensioning the mains contactor

Notes
(1) Limit value for first environment is also relevant, if source of
interference of second environment affects first environment
(2) Designations "class" and "group" according to IEC CISPR
11
QSP: Measuring method quasi peak measurement; AV: Meas‐
uring method arithmetic averaging
Fig. 4-28:
Limit Values for Line-Based Disturbances (IEC 61800-3); Limit Value
Characteristic through Frequency Range
When using mains chokes, take their effect on the connected drive control‐
lers into account. Due to their inductance, mains chokes have a smoothing
effect on the current and thereby reduce harmonics.
Take the nominal current of the mains choke into account to have the induc‐
tance of the mains choke available.
Some mains chokes are assigned to certain drive controllers (see technical
data of the drive controller "Data for mains voltage supply → Assigned type of
mains choke").
Required data:
Nominal current I
LN
voltage" on page
233)
Number of drive controllers connected to the mains contactor
When using mains contactors of the utilization category AC-1, observe the
conventional thermal continuous current I
tor) when dimensioning the mains contactor.
The minimum required conventional thermal continuous current I
from the sum of nominal currents Σ I
DOK-INDRV*-HCS01******-PR05-EN-P
Rexroth IndraDrive CsDrive Systems with HCS01
of the drive controller (see
(see data sheet of mains contac‐
th
of all connected drive controllers.
LN
chapter 7.3.2 "Mains
results
th