Optional Connection Points - Bosch Rexroth IndraDrive CsDrive System with HCS01 Project Planning Manual

Hide thumbs Also See for Rexroth IndraDrive CsDrive System with HCS01:
Table of Contents

Advertisement

DOK-INDRV*-HCS01******-PR05-EN-P
Rexroth IndraDrive CsDrive Systems with HCS01
6.2.4

Optional connection points

X8, Optional Encoder (Option EC)
X8, Encoder Emulation (Option EM)
Description
View
D-Sub 15-pin, male
Connection cable
Stranded wire
Emulated Encoder Systems
Connec‐
Signal
tion
1
n. c.
2
UL
3
SSI_CLK+
4
SSI_CLK-
5
n. c.
6
ULA0
7
ULA1
You can connect an optional encoder to connection point X8.
Technical data: See
Emulation of absolute value and incremental encoder signals for further eval‐
uation by a control unit. The signals are galvanically isolated from the circuit
board.
Identifica‐
tion
X8
Unit
mm
Tab. 6-22:
Function, Pin Assignment, Properties
Incremental encoder
SSI encoder
Incremental encoder with signal level converter
Pin Assignment
Level
Input/
Function
Output
-
-
Not assigned
5 ... 30 V
In
Power supply for output driver
RS422
In
SSI clock positive
RS422
In
SSI clock negative
-
-
Not assigned
UL
Out
Reference track with UL level
UL
Out
Track A1 with UL level
description of connection point
Encoder emulation
Min.
0,25
2
Bosch Rexroth AG
159/341
Mounting and installation
X4.
Function
Max.
0,5
Incremen‐
SSI en‐
Incremen‐
tal encod‐
coder
tal encod‐
er
er with
signal lev‐
el convert‐
er

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents