6.
Rotate the enclosure, if necessary, to allow removal of the IMV:
a.
Using a ½ inch hex socket with ratchet, loosen the µFLO enclosure
mounting clamp bolts and rotate the enclosure a sufficient distance to allow
removal of the IMV, approximately 11 inches (28 cm).
CAUTION – Equipment damage. When rotating the enclosure, be
careful to not stress or damage the wires and cables connected through
the enclosure access points.
b.
After rotation, tighten the clamp bolts to hold the µFLO in place.
7.
Remove the IMV assembly:
a.
Using a phillips screwdriver, remove the eight (8) mounting screws,
washers and lock washers, located on the bottom of the enclosure, that
secure the IMV to the µFLO cabinet (Figure 5, µFLOG5 assembly,
exploded view, page 11). Be careful not to drop the screws.
b.
Loosen the IMV by tilting it slightly forwards and then backwards. Carefully
slide the upper body of the assembly down through the bottom access
cutout until clear.
c.
The weather-sealing gasket is affixed to the top side of the IMV mounting
flange and may be stuck to the bottom of the enclosure. Remove any
remaining gasket that is adhered to the bottom of the cabinet.
CAUTION – Equipment damage. The gasket area should be clean and
free of any materials that may hinder the seal of a new gasket. An
improper gasket seal may allow moisture or dirt to enter the enclosure
and damage the electronic components.