External Wiring 5-1 To - Hitachi HIDIC EH-150 Instruction Manual

Resistance thermometer input module(eh-pt4)
Hide thumbs Also See for HIDIC EH-150:
Table of Contents

Advertisement

5. External Wiring
5.1 Wiring
PT100
PT100
External wiring(Note1)
Use a shilded cable
PT100
Grounding (Note2)
Note 1: The external wire length should be less than 200 m for each channel. In addition, the total resistance of the
wires of each channels to be connected to the current terminals (A0 to A3, B0 to B3) should be less than 400
ohm.
Note 2: Earth the shield of the cable for the one side or the both sides, which depends on the environment.
Note 3: The earth terminal on the power supply module and External power supply 24 VDC must be connected
to the earth, otherwise the data will be undefined.
5. External Wiring
×
×
×
×
×
×
×
×
×
External power supply
24VDC
Fig. 5.1 External Wiring
5-1
b0
A0
A0 to 3 : Current terminal
×
B0 to 3: Cuurent terminal
B0
b0 to 3: Voltage terminal
NC
×
b1
A1
×
B1
NC
×
b2
A2
×
B2
Make a Short-circuit on
NC
unused channel, shown as the
×
figure. The data will be
b3
H7FFF. Otherwise it will be
A3
×
undifined.
B3
NC
×
+24V
-24V
×

Advertisement

Table of Contents
loading

Table of Contents