Procedure
Step 1 Connect signal cables to corresponding signal connectors.
Figure 5-25 Assembling a signal connector (single SUN2000)
Issue 01 (2020-04-17)
In the scenario of balanced three-phase grid connection, if the SUN2000s requires the grid-tied point
control function, they need to be connected to a three-phase power meter to control the total
three-phase power.
If there is only one battery, connect the battery to the master SUN2000. If there are multiple batteries,
connect one battery to the master SUN2000 and the other batteries to the slave SUN2000s.
Ensure that the protection layer of the cable is in the connector. The surplus core should be
cut off from the protection layer.
Ensure that the exposed core is totally inserted into the cable hole.
Ensure that the signal cables are connected securely.
Ensure that the cables are not twisted.
If multiple signal cables need to be connected to a single connector, ensure that the outer
diameters of the signal cables are the same.