17.2

Sensor curves

WARNING:
Danger to life from electric current!
Touching live parts can result in an electric shock.
▶ Prior to every measurement, disconnect the power supply
completely from the heating system.
▶ Always measure the temperatures being compared (room, flow,
outside and flue gas temperatures) near the relevant sensor.
The curves depict mean values and are subject to tolerances.
▶ Measure the resistance at the cable ends.

17.2.1 Temperature sensor at digital burner control unit

Temperature sensor resistance values at digital
burner control unit
Temperature
Minimum value
[ °C]
[
5
23466.20
10
18770.80
15
15120.00
20
12245.80
25
9951.30
30
8145.40
35
6711.50
40
5560.60
45
4625.40
50
3866.90
55
3239.10
60
2730.20
65
2314.50
70
1969.90
75
1683.30
80
1444.90
85
1241.90
90
1073.10
95
927.60
100
805.20
Table 22 Resistance values
2 similar temperature sensors (twin sensors), which are installed in a
single sensor casing, are used as boiler water temperature sensors.
All temperature sensors in the boiler have the same sensor curve.
Condens 7000 F – 6720871560 (2019/11)
Nominal value
Maximum value
[
[
24495.00
25523.80
19553.00
20335.20
15701.00
16282.00
12690.00
13134.20
10291.00
10630.70
8406.00
8666.60
6912.00
7112.50
5715.00
5869.40
4744.00
4862.60
3958.00
4049.10
3312.00
3384.90
2786.00
2841.80
2357.00
2399.50
2004.00
2038.10
1709.00
1734.70
1464.00
1483.10
1257.00
1272.10
1084.00
1094.90
938.90
950.20
815.90
826.60
17.3

Hydraulic resistance

1000
150 kw
75/100 kw
100
10
y
250 kw
1
1000
x
Fig. 72 Flow resistance on the heating water side
x
Volumetric flow rate (l/h)
y
Pressure drop on the heating water side (mbar)
17.4

Connection diagrams

17.4.1 Control unit connection diagram

▶ To connect the control unit, observe the corresponding technical
documentation and the connection diagram for the specific control
unit.
DANGER:
Danger to life from electric current!
▶ Never use the earth conductor (green/yellow) as a control cable.
NOTICE:
System damage with incorrect installation!
▶ Provide a permanent power supply (not a safety plug).
▶ Ensure that the power supply is connected to the correct phases.
▶ Select the installation, fuse/circuit breaker rating, ON/OFF switch,
emergency stop switch and safety measures in accordance with local
regulations.
Appendix
200 kw
300 kw
10000
100000
0010012496-001
59