MOD BU S TC P MA PP ING
– Access to configuration options
For access to configuration options, use the following log-in:
Username = admin
Password = admin
– Access to monitoring screens
For access to monitoring screens only, use the following log-in:
Username = monitor
Password = monitor
3.5

Modbus TCP Mapping

The AWIN GW100 gateway can function as a protocol converter by mapping the HART com-
mand data from the WirelessHART network to Modbus TCP registers. This allows for easy in-
tegration of HART data into Modbus TCP host system.
3.6

Network Topology View

The AWIN GW100 gateway's web interface provides a table with connectivity information of
WirelessHART devices. It also shows the strength of wireless mesh network in a color-coded
format.
3.7

Ethernet Network Connectivity

AWIN GW100's Ethernet port shall be connected to an Ethernet switch. The switch can be
part of a host network. A typical host system on the host network could be a PLC or Automa-
tion controller using ModbusTCP protocol to communicate to the gateway.
3.8

Hard Reset

A hardware reset restores the default IP address of
sets the AWIN GW100 to factory default settings.
18
The user must change password after first login or at least before commission-
ing the gateway.
The ethernet switch port connected to the AWIN GW100 gateway shall have Flow
Rate limiter enabled. Overall bandwidth should be capped to 10Mbps (recom-
mended). Avoid mixing field network with other networks, such as control and cli-
ent/server network. AWIN GW100 belongs to a field network only.