Part Identification Nomenclature - Mitsubishi Electric MELSEC Q Series User Manual

Channel isolated digital-analog converter module
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

4
SETUP AND PROCEDURES BEFORE OPERATION

4.3 Part Identification Nomenclature

4 - 3
The name of each part in the Q62DA-FG is listed below.
1)
2)
4)
Number
Name
1)
RUN LED
2)
ERR. LED
3)
ALM LED
External power
4)
supply terminal
Serial number
5)
plate
1 Check Error code for details.
3)
5)
Displays the operating status of the Q62DA-FG.
On
: Normal operation
Flashing : During offset/gain setting mode
Off
: 5V power supply interrupted, watch dog timer error, 5V power
switched off, watchdog timer error occurred, or Online module
change enabled.
Displays the error status of the Q62DA-FG.
1
On
: Error
Flashing : Error in switch settings
Switch No. 5 of the intelligent function module has been set to a
value other than zero "0".
Off
: Normal operation
Indicates the warning status of the Q62DA-FG.
On
: During warning output occurrence
Flashing : During disconnection detection
Off
: Normal operation
This is the terminal for connecting the 24 V DC external power supply.
Indicates the serial No. of the Q62DA-FG.
MELSEC-Q
Description