5 PROGRAMMING

5.6.2 Program example in a combination with the S10V LPU

S012: System register that performs a one-sequence cycle ON
S012
S012
S012
S012
* In the program example, the FL000, FL100, FW100, and FW101 registers are used. When the
program is applied to actual facilities, replace them with registers that are not used in other
circuits.
operation when the ladder status changes from STOP to RUN.
Sets an unused parameter area (mathematical/logical
function MOV instruction) to "0."
MOV H4B200200 = BD008
F
MOV 700 = BD009
F
MOV 5 = BD00A
F
MOV 0 = BD00C
F
MOV HA20009C2 = BD00D
F
MOV 1 = BD00E
F
MOV H44570A00 = BD010
F
MOV H52200BB8 = BD020
F
MOV 200 = BD030
F
MOV H44570B00 = BD014
F
MOV H52200CB2 = BD024
F
MOV 32 = BD034
F
MOV H8F3B02 = FL000
F
MOV 50 = FW100
F
MOM FW100 : 1 = W(FL000)
F
MOV H8F3B00 = FL002
F
MOV 1 = FW101
F
MOM FW101 : 1 = W(FL002)
F
5-16
: Sets the status display/
control register to K200.
: Sets the response wait time
to 700 ms.
: Sets the communication
retry count to 5.
: Sets the communication
protocol to 0.
: Sets the remote station IP
address to 162.0.9.194.
: Selects the "no endian
conversion" option.
: Sets the S10V transmission
area to DWA00.
: Sets the MELSEC write area
to R0BB8.
: Sets the transmission word
count to 200.
: Sets the S10V reception
area to DWB00.
: Sets the MELSEC read area
to R0CB2.
: Sets the reception word
count to 32.
: Sets the delay time setting
area address.
: Sets the delay time set point
to 50 ms.
: Sets to the inside of the
module.
: Sets the start flag area
address.
: Sets start flag set point.
: Sets a communication start.