Smoke Detector - Huawei FusionModule500 Product Description

Smart mini data center
Hide thumbs Also See for FusionModule500:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
Silk Screen
AI/DI_1 to
AI/DI_8
The AI/DI module is configured with a 4-bit DIP switch. Set toggle switches 1 to 3 to
configure the address of the AI/DI module, and set toggle switch 4 to enable or disable the
build-out resistor for the RS485 port.
Table 3-22 Mapping between the independent deployment AI/DI unit address and the DIP switch
settings
Address
1
2

3.4.4 Smoke Detector

A smoke detector detects smoke around cabinets.
Issue 05 (2019-11-22)
Port Description
Provide 12 V DC outputs for sensors and are compatible with 4 mA to
20 mA current signals, signals from current-based smoke sensors and
water sensors, dry contact signals, and NTC signals.
Pin definition:
3: 12 V DC, 54 mA
6: D–
7: D+
8: GND
SW1
OFF
ON
If the signal quality is poor due to signal reflection caused by long communications cables (longer than
50 m), set toggle switch 4 to ON for the furthest independent deployment AI/DI unit. After the DIP
switch settings are modified, power off and restart the independent deployment AI/DI unit for the new
settings to take effect.
Copyright © Huawei Technologies Co., Ltd.
SW2
ON
OFF
3 System Architecture
SW3
ON
ON
42

Advertisement

Table of Contents
loading

Table of Contents