Wiring example for voltage output type
The wiring example for the DC input module (1) and the voltage output type (2) is shown below.
(1)
COM
Output
X0
0V
Power supply
for sensor
When connecting to the voltage output type (1) sensor, avoid the wiring as shown below.
In the wiring below, a current flows into the DC input module through the pull-up resistor (2) in the sensor. As
a result, an input current may not reach the ON current of the DC input module (3), which does not change the
input signal to an ON state.
(3)
COM
(2)
(1)
Power supply
for sensor
(2)
Output
X0
0V
6 INSTALLATION AND WIRING
6.3 Input Wiring Examples
6
109