PARAMETER SETTINGS
This chapter describes the parameter settings of the I/O modules. Setting parameters here eliminates the need to program
them.
7.1

Parameter Setting Procedure

1.
Add the I/O module to the setting in the engineering tool.
[Navigation window]  [Parameter]  [Module Information]  Right-click  [Add New Module]
2.
The parameter setting consists of four items: the input response time setting, interrupt setting, setting of error-time output
mode, and refresh setting. Select these items from the tree window below to set them.
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Module Parameter]
3.
Write the setting into the CPU module using the engineering tool.
[Online]  [Write to PLC]
4.
Reset the CPU module or turn off and on the power to reflect the setting.