Communication System Manual
Note
!
Response from slave
The slave responds to a configuration message with "E5H" (short acknowledge). If the slave detects
discrepancies as compared with the entries in the GSD file, it report the configuration errors later when it
receives a diagnostic request from the master. It is not ready for user data traffic in this case.

4.5.6.3 Diagnostics

Diagnostic data are high-priority data. The DP/3WN1, 3WS1 interface module generates external
diagnostics if the connection to the external device (3WN1/3WS1 circuit-breaker) is faulted.
The diagnostic information of a DP slave includes standard diagnostic information (6 bytes) and possibly
user-specific diagnostic information.
The diagnostic request message from the master is structured as follows:
SD
LE
68H
x
The diagnostic response message from the interface is structured as follows:
110
Class 2 master
If the actual configuration is not known to the class 2 master, it can first read the slave
configuration using "Get_Cfg" and then send it to the slave to be checked. This service
program is especially useful for modular systems.
LEr
SD
DA
SA
x
68H
8x
8x
© Copyright Siemens AG 1998. All rights reserved.
3WN1, 3WS1 Circuit-Breakers
FC
DSA
SSA
FCS
P
P
x
60/3
62/3
x
C
E
ED
16H
Version 1.0 (08/98)