Communication System Manual
RELEASE
3WN6 output data (cyclic)
Ready to close
Load shedding
Reserved
Phase number for main actual value
Phase number for main actual value
Group error signal
Group warning signal
Group fault signal
"Tripped" signal not acknowledged
Electrical closing lockout
Storage spring charged
Circuit-breaker OFF
Circuit-breaker ON
Current in highest loaded phase
L
, L
or L
1
2
3
55)
The "group error signal" is set (= 1) of one bit of "processor status" (message 1:5, page 45) is set. Similarly, the "group warning signal" is set (= 1) of
one bit of "warning signals" (message 1:3, Seite 44) is set and "group fault signal" is set if one bit of "Tripped signals" (message 1:2, page 43) is set. An
additional option for releases N and P when used in conjunction with the communication module with measurement functions (Z=F05) is to apply the
"fault signals" (message 1:8, Page 46) to either the "group warning signal" (for OS1:2 = 0) or the "group fault signal" (for OS1:2 = 1) by means of
"additional functions 1" (message 1:121, Page 50).
58
OCTET 9
55)
53)
53)
OCTET 10
OCTETS 11 and 12
[A]
© Copyright Siemens AG 1998. All rights reserved.
Time response of communication
(Duration of read/write operations
and update rate for values in 3WN6)
BIT 15
It takes approx. 150 ms to read cyclic data in
BIT 14
the PLC I/O area of 3WN6. The cyclic data are
BIT 13
updated within 3WN6 approx. every 700ms.
BIT 12
BIT 11
BIT 10
BIT 9
BIT 8
BIT 7
BIT 6
as above
BIT 5
BIT 4
BIT 3
BIT 2
BIT 1
BIT 0
as above
3WN6 Circuit-Breakers