Communication System Manual
RELEASE
PLC input data from 3WN6
(cyclic)
Ready to close
Load shedding
Reserved
Phase number for main actual value BIT 12
Phase number for main actual value BIT 11
Group error signal
Group warning signal
Group fault signal
"Tripped" signal not acknowledged
Electrical closing lockout
Storage spring charged
Circuit-breaker OFF
Circuit-breaker ON
OCTETS 11 and 12
Current in highest loaded phase
L
, L
or L
1
2
51)
The "group fault signal" is set (= 1) of one bit of "processor status" (message 1:5, page 45) is set. Similarly, the "group warning signal" is set
(= 1) of one bit of "warning signals" (message 1:3, Seite 44) is set and "group fault signal" is set if one bit of "Tripped signals" (message
1:2, page 43) is set. An additional option for releases N and P when used in conjunction with the communication module with measurement
functions (Z=F05) is to apply the "fault signals" (message 1:8, Page 50) to either the "group warning signal" (for OS1:2 = 0) or the "group
fault signal" (for OS1:2 = 1) by means of "additional functions 1" (message 1:121, Page 50).
52)
Acknowledgement either by means of "Clear" button on the release unit or by means of bit 8 of the circuit-breaker output data. The
acknowledgement generates a reset of the group fault signal and of all "Tripped" signals for which the trip cause is no longer present.
Version 1.0 (05/98)
OCTET 9
51)
49)
49)
OCTET 10
[A]
3
© Copyright Siemens AG 1998. All rights reserved.
N and P
BIT 15
X
BIT 14
X
BIT 13
X
X
X
BIT 10
X
BIT 9
X
BIT 8
X
BIT 7
52)
BIT 6
X
BIT 5
X
BIT 4
X
BIT 3
BIT 2
BIT 1
X
BIT 0
X
X
3WN6 Circuit-Breakers
H and J/K
D and E/F
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
53