Chapter 6 Wiring; Wiring Precautions; Connector For External Devices - Mitsubishi Electric MELSEC- iQ-R Series Startup User's Manual

Channel isolated analog-digital converter module
Hide thumbs Also See for MELSEC- iQ-R Series:
Table of Contents

Advertisement

6
WIRING
This chapter describes the wiring of the A/D converter module.
6.1

Wiring Precautions

Connector for external devices

Precautions
Tighten the screws within the specified torque range.
Screw type
Module fixing screw (M3 screw)
Connector screw (M2.6 screw)
*1 The A/D converter module can be easily fixed to the base unit with the hook(s) located at the top. However, in places where a vibration
occurs frequently, fix the module with module fixing screws.
• Use copper wire with a temperature rating of 75 or higher for the connector.
• Use UL listed connectors if necessary for UL compliance.
Applicable connectors
Connectors for external devices to be used for the A/D converter module are sold separately.
The following table lists the connector types.
■40-pin connector
Type
Soldering type connector (straight type)
Crimping type connector (straight type)
Soldering type connector (dual purpose (straight/oblique) type)
*1 When using 40 pins, use cables whose sheath outside diameters are 1.3mm or shorter.
Select wires suitable to the current value used.
• The A6CON3 (IDC type connector (straight type)) cannot be used.
• The connector/terminal block converter module and the dedicated cables that are designed for the
MELSEC-Q series channel isolated analog module can be used. For details, refer to the following.
Page 29 When the connector/terminal block converter module is used
■40-pin connector crimping tool
Type
Crimping tool
For how to wire the connector and how to use the crimping tool, contact FUJITSU COMPONENT LIMITED.
Wiring method, installation procedure, and disconnection procedure of the connector
For the wiring method, installation procedure, and disconnection procedure, refer to the following.
 MELSEC iQ-R Module Configuration Manual
6 WIRING
26
6.1 Wiring Precautions
*1
Tightening torque range
0.36 to 0.48Nm
0.20 to 0.29Nm
Model
*1
A6CON1
A6CON2
*1
A6CON4
Model
FCN-363T-T005/H
Applicable wire size
0.088 to 0.3 (28 to 22 AWG), (stranded wire)
0.088 to 0.24 (28 to 24 AWG) (stranded wire)
0.088 to 0.3 (28 to 22 AWG), (stranded wire)
Contact
FUJITSU COMPONENT LIMITED

Advertisement

Table of Contents
loading