Parameter settings
Perform initial settings in the parameter settings of the engineering tool. The auto refresh setting does not need to be changed
here.
For the parameters not to be set, their default values are used.
Function
Setting item
Range switching function
Input range setting
A/D conversion enable/
A/D conversion enable/disable
disable setting function
setting
A/D conversion method
Averaging process
specification
Time average/Count average/
Moving average/Primary delay
filter constant setting
Conversion start time
Conversion start time setting
setting function
Scaling function
Scaling enable/disable setting
Scaling upper limit value
Scaling lower limit value
Shift function
Conversion value shift amount
Digital clipping function
Digital clipping enable/disable
setting
Warning output function
Warning output setting
(process alarm)
(process alarm)
Process alarm upper upper
limit value
Process alarm upper lower limit
value
Process alarm lower upper limit
value
Process alarm lower lower limit
value
Warning output function
Warning output setting (rate
(rate alarm)
alarm)
Rate alarm warning detection
cycle setting
Rate alarm upper limit value
Rate alarm lower limit value
Input signal error detection
Input signal error detection
function
setting
Input signal error detection
lower limit setting value
Input signal error detection
upper limit setting value
CH1
CH2
CH3
4 to 20mA
4 to 20mA
(2-wire
(Current
transmitter
input)
input)
A/D
A/D
A/D
conversion
conversion
conversion
enable
disable
enable
Sampling
Count
processing
average
50
10.0s
3.0s
Disable
Disable
0
0
Disable
Disable
Disable
Enable
32000
28000
4000
0
Enable
Disable
400 times
25.0%
-5.0%
Upper limit
Disable
detection
8.0%
CH4
CH5
CH6
0 to 20mA
4 to 20mA
(Current
(2-wire
input)
transmitter
input)
A/D
A/D
A/D
conversion
conversion
conversion
disable
enable
enable
Moving
Sampling
average
processing
10
3.0s
3.0s
Enable
Disable
16000
2000
2000
0
Enable
Disable
Disable
Disable
Disable
Disable
Disable
Disable