Mitsubishi Electric 800 Series Instruction Manual page 118

Connection
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

Fault
Protective
function
Alarm,
Warning, Error
message
Surrounding air temperature
Surrounding air humidity
*6
Storage temperature
Ambience
Altitude/vibration
*1
Available when a Vector control compatible option (FR-A8AP E kit) is installed.
*2
Available only for the standard model.
*3
Available for the Ethernet model and the safety communication model.
*4
Available for the three-phase power input model.
*5
Not activated in the inverter in the initial state.
*6
Applicable to conditions for a short time, for example, in transit.
*7
For the installation at an altitude above 1000 m, consider a 3% reduction in the rated current per 500 m increase in altitude.
Overcurrent trip during acceleration, Overcurrent trip during constant speed, Overcurrent trip during
deceleration or stop, Regenerative overvoltage trip during acceleration, Regenerative overvoltage trip
during constant speed, Regenerative overvoltage trip during deceleration or stop, Inverter overload
trip (electronic thermal relay function), Motor overload trip (electronic thermal relay function), Heat
sink overheat, Undervoltage, Input phase loss
*5
detection
, Upper limit fault detection, Lower limit fault detection, Brake transistor fault, Output side
earth (ground) fault overcurrent, Output short circuit, Output phase loss, External thermal relay
operation, Option fault, Communication option fault, Parameter storage device fault, PU
disconnection, Retry count excess, CPU fault, Abnormal output current detection, Inrush current limit
circuit fault, USB communication fault, Analog input fault, Safety circuit fault, Overspeed occurrence
Speed deviation excess detection
fault, Ethernet communication fault, Opposite rotation deceleration fault
definition error by the PLC function, Board combination fault
Fan alarm, stall prevention (overcurrent), stall prevention (overvoltage), regenerative brake pre-
*5
alarm
, electronic thermal relay function pre-alarm, PU stop, maintenance timer alarm, parameter
*5
write error, operation panel lock
*3
communication fault
, duplicate IP address
-20°C to +60°C (The rated current must be reduced at a temperature above 50°C.)
95% RH or less (non-condensing) (With circuit board coating (conforming to IEC 60721-3-3 3C2))
90% RH or less (non-condensing) (Without circuit board coating)
-40°C to +70°C
Indoors (free from corrosive gas, flammable gas, oil mist, dust and dirt)
*7
2
Maximum 3000 m
, 5.9 m/s
or less at 10 to 55 Hz in X, Y, and Z directions
*4
, Stall prevention stop, Loss of synchronism
*1*5
*1*5
, Signal loss detection
, Brake sequence fault
, Password locked, speed limit indication, safety stop, Ethernet
*3
*3
, IP address fault
, incorrect parameter setting
*5
,
*5
, PID signal
*5
, Internal circuit fault, User
117
4. Specifications
4.3 Common specifications
1
2
3
4
5
6
7
8
9
10