Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication
Protocols
.
3.2.31 X-SIA text (Message Type <TAB>)
X-SIA Example
SIA Mode Description
<LF><CRC><TAB><sequence#><receiver#><line#>[#aaaa|EMMZZZZ*'TTTTTTTTTTTTT'NM/***
]<CR>
Table 91: X-SIA text (Message Type <TAB>) Byte Description
Title
LF
CRC
Message Type
sequence#
receiver#
line#
(Line/Group #)
account #
E
MM
ZZZZ
*
`
TT...TTT
'
NM
/
***
Figure 25: Message sent to printer
MM/DDsHH:MMsLxxsSIAsACCTsAAAA
+++sEMMZZZZ*'TTTTTTTTTTTTT'NM
+++sEMMZZZZ*'TTTTTTTTTTTTT'NM
Bosch Security Systems, Inc. | 2012.09 | 4998122703-05
Description
Standard line feed character.
Cyclical redundancy check number.
<TAB>
The message sequence number. The valid sequence number range is 0001
to 9999.
The receiver gateway that sent the message. Valid digits: 01 to 99 for
D6600/D6100/D6100IPv6.
The line number of the line in the receiver gateway that sent the message.
Valid digits: 00 to 99. The receiver uses Line 0 (zero) for internal
messages.
The communicator's account number has up to 16 digits.
SIA block code.
SIA event code.
Zone number.
Text identifier.
Single quote.
13 character text string.
Single quote.
Unit field characters.
Separator.
Next data.
75

Advertisement

Table of Contents
loading

This manual is also suitable for:

Conettix d6100ipv6Conettix d6100i

Table of Contents