Zone address (Zone No.)
• "Zone address" is to be set when the central remote controller is used for each zone.
Zone address is set by switch setting on central remote controller.
Central remote controller can divide all indoor units into max. 4 zone.
The zone to which the indoor unit belongs is decided by its central control address.
Central control address
Header
Central remote
controller
("All" mode)
Outdoor unit
Zone
address
Indoor unit
Remote
controller
Central
1
control
address
(At shipment=99, Address unset)
Zone No.
1 to 16
Zone 1
17 to 32
Zone 2
33 to 48
Zone 3
49 to 64
Zone 4
Follower
Zone 1
1
Central
Zone 1 RC*
2
3
4
Header
Follower
Zone 2
Central
Zone 2 RC*
17
18
19
* RC: Remote controller
60
Header
2
20
21