4-4 Address setting for Control System devices
4-4-1 address setting flow
Before setting for TCS-NET air conditioning system, be sure to complete address setting and trial
operation of each air conditioning system.
(Address setting --- Line/Group/indoor unit address, central control address if central controller exists
Trial operation --- Test operation should be performed in each refrigerant system one by one.)
Setting flow
Intelligent Server setting
TCS-Net relay I/F setting
Energy monitoring exist ?
Energy monitoring relay I/F setting
Digital I/O relay I/F exist ?
Digital I/O Relay I/F setting
Power ON (Trial Operation)
CAUTION
Contents
CF card mounting, Dip switch setting
Address setting (SW01 on P.C. Board,
address 1 to 8)
Terminator Resistor setting (SW06 on P.C.
Board)
Address setting (SW01 on P.C. Board,
address 1 to 4)
Address setting (SW01 on P.C. Board,
address 1 to 4)
91
Reference No.
4-4-2
4-4-3
4-4-4
4-4-5
Chapter. 5