Toshiba BMS-TP0640ACE Manual page 68

Touch screen controller, tcs-net air conditioning control system
Table of Contents

Advertisement

4-3-1 (7) Setup of relay connector and terminator
• After trial operation for each refrigerant system, set the relay connector and terminator resistor for all
refrigerant system which are connected from one TCS-NET relay interface.
<Procedure>
1
How to set up terminator resistor (SW30)
When all the address setups have finished in the same
refrigerant system, put the terminator resistor (SW30) in the
same central control line into one.
• Remain only SW30-2 of the header outdoor unit with the
least line address number as it is ON.
(With terminal resistor)
• Set up SW30-2 of the other header outdoor units to OFF.
(Without terminal resistor)
2
Connect the relay connector between [U1U2] and
[U3U4] of the header outdoor unit for each refrigerant
system.
<System diagram (example)>
Ethernet
Touch Screen Controller
(BMS-TP0640/5120)
PC for Energy
Monitoring
Range for each
setting procedure
RS-485
InteIligent Server
(BMS-LSV2E)
Compact
Flash
InteIligent Server
Software
(BMS-STCC01E)
Switching HUB
Main BUS
TCS-NET
Relay I/F
(BMS-IFLSV1E)
No.1
Main BUS
TCS-NET
Relay I/F
(BMS-IFLSV1E)
No.2
Main BUS
TCS-NET
Relay I/F
(BMS-IFLSV1E)
No.3
68
Header outdoor unit
interface P.C. board
ON
1
SW30
ON
ON
ON
1
2 3 4
1
2 3 4
1
2 3 4
SW11
SW12
SW13
ON
ON
ON
ON
1
2 3 4
1
2 3 4
1
1
SW06
SW07
SW08
2
U1 U2
For internal
For wiring of
wiring between
central control
indoor and
system
outdoor
Main BUS
Main BUS
Main BUS
1
2
SW30
ON
1
2 3 4
SW14
ON
2 3 4
1 2 3 4
SW09
SW10
U3 U4
U5 U6
For internal
wiring between
outdoor units
Line address
=1
Line address
=2
Line address
=3
Line address
=4
Line address
=5
Line address
=6