2.3 How to set current rating, trip characteristic, sensitive current and oper-
ating time

2.3.1 Cautionary instructions for setting

Let a person having technical knowledge of electricity set the breaker.
Before setting, turn off the upper circuit breaker, or turn off the circuit breaker to be set or trip
the breaker, then make sure of no current conducting.
Otherwise, electrification can result.
Procedure 2: With a detector, make
sure of no current conducting.
2.3.2 How to set characteristics of molded-case circuit breakers [electronic overcurrent
tripping type]
Applicable
NF125-SGW(RE), NF125-HGW(RE), NF160-SGW(RE)
model
NF160-HGW(RE), NF250-SGW(RE), NF250-HGW(RE)
Layout of
Trip (PTT)
setting dials
button
CAUTION
Group A
70%LED (green)
PAL LED (yellow)
OVER LED (red)
Setting dial
Button cover
Procedure 1: Turn off the upper
circuit breaker.
Circuit breaker to be set
Group B
NF400-SEW, NF400-HEW, NF400-REW, NF400-UEW
NF630-SEW, NF630-HEW, NF630-REW, NF800-CEW,
NF800-SEW, NF800-HEW, NF800-REW, NF800-UEW
NF1000-SEW, NF1250-SEW, NF1600-SEW
Rated current label
OVER LED (red)
Trip
PAL LED (yellow)
(PTT) button
70% LED (green)
Replacement label
Cover
Setting dial
Connection cover
10