Troubleshooting; Troubleshooting For Circuit-Breaker Proper (Mccb/Elcb) - Mitsubishi Electric C Series Handling And Maintenance

Moulded case circuit breakers, earth leakage circuit breakers, earth leakage relays & circuit protectors
Table of Contents

Advertisement

5. Troubleshooting

5.1 Troubleshooting for circuit-breaker proper (MCCB/ELCB)

Trouble
Foreign matter in switching mechanism
Closing impossible
No resetting
Resetting impossible
Wear due to trip endurance
Poor reset mechanism
(*) Resetting impossible
Non-excitation of undervoltage coil
Tripping impossible
Resetting time has not elapsed
OFF impossible
Breakage and/or fatigue of the
switching spring
Fusion of contact due to excessive interruptive current
Excessive operation power
Poor positional relationship between the external handle and the
circuit-breaker
Excessive shock from exterior
Insulating material mingled between contacts
Corrosion by infiltrating rain water, etc.
Fused conductive portion
Large consumption of contact
Breakage of rated changeover screw
Excessive tightening torque (tighten with 3 to 4.5 kg-cm of torque)
Too high an ambient temperature
Too high a temperature rise
Troublesome operation
Deviation of applied frequency (thermal-
under normal load
adjustable electromagnetic type 800AF or higher)
Load current strained with much high component
Rather small measurements by error of measuring instrument due to distorted current
Too small a setting of rated current
Electronic
Overcurrent
Tightening forgotten of the changeover screw of rated current
type
display
Failure of rated current changeover portion
MCCB
LED is on
Exothermic reaction due to repeated starting current
Erroneous action while
starting
Too long a starting time
Too high a starting current
Too high a starting rush current
Transient current when changing delta connection to star one. Transient current due to reversible operation
Instantaneous action
Rush current at the time of instantaneous restart
during starting
Rare short-circuit of motor
Bimetal reset incomplete after instantaneous tripping
Abnormal current running simultaneously with closing (short-circuit closing)
Transmission was made with antenna of transceiver (5W or higher)
Operating while in use
closely mounted on the electronic MCCB and earth leakage breaker
Shift from the short-circuit of another conductor
Short-circuit on line side
Accumulated dust
Fall of conductor on line side
Poor tightening
Too high a temperature on
Contact heavily consumed
the terminal side
Increased contact resistance
Complete electromagnetic type used in high frequency (400 Hz, for instance)
Too high a temperature on
Load current distorted containing much high frequency component
the lateral side of the
Erroneous measurement dependent on feeling
mould
Loosened stud
Exothermic reaction of the
Poor contact between the conductive portion of stud and the body terminal
tightened portion of stud
Groove machining forgotten for reduction of eddy-current exothermic reaction of rear-connected type iron mount plate (400AF or higher)
Too high a rated current selected
No tripping with over
Wrong frequency applied
current
Tripping of backup circuit-breaker
Overcurrent display LED does
not come on. Or, though it
The battery of breaker tester has come at the end of its service life.
comes on, it goes off sonner
than normal.
Overcurrent display LED comes
Poor tripping mechanism
on and goes off after prescribed
time. But, no tripping.
79
Cause
See below (*)
Incessant use of voltage trip operation
End of service life
Poor adjustment
Carelessness
Breakage by initial trouble
End of service life
Excessive interrupting current
Short-circuit current cut off. End of service life
Application of overcurrent
Erroneous selection (temperature correction)
Board hermetically closed
Loosened connection to terminal
Erroneous selection (frequency)
Erroneous selection
Erroneous selection
Poor maintenance
End of service life
Intrusion of rust and dust
Too low a current for instanta-
neous tripping of backup breaker
Countermeasure
Foreign matters to be removed
To be reset once again
See below
To be replaced with new one, Voltage trip to be replaced by electric operation
To be replaced with new one
To be returned for repairing
To be excited
Wait until the bimetal is cooled down
To be returned for repairing
To be replaced by new one
To be replaced by circuit-breaker with large breaking capacity
Handle to be replaced
Handle to be replaced
Revision of positional relationship
To be replaced with new one
Foreign matter to be removed (with removable cover)
To be returned for repairing (with unremovable cover)
To be replaced with new one
To be replaced by new one with larger breaking capacity
To be replaced with new one
To be returned for repairing
Rating selection to be changed
Ventilation
Retighten
To be replaced with circuit-breaker of suitable frequency
Distortion factor to be decreased by reactor
To be measured correctly by a meter with true effective value, and correct selection of rating
Correct the setting of rated current
Correct retightening of the rated current changeover screw with tightening torque: 3 to 4.5 kg-cm
To be returned for repairing
To be replaced by a unit with higher rating
To be replaced by a unit with higher rating
Electromagnetic setting to be change or the unit to be replaced by one with higher rating
Electromagnetic setting to be change or the unit to be replaced by one with higher rating
Electromagnetic setting to be change or the unit to be replaced by one with higher rating
Electromagnetic setting to be change or the unit to be replaced by one with higher rating
Motor to be repaired
To be fully restored
Circuit to be checked to remove the cause
Transceiver to be used at a distance at least 1 m from the electronic
MCCB
Cause to be removed To be replaced with new one
Cause to be removed To be replaced with new one
Cause to be removed To be replaced with new one
Retighten
To be replaced by new one
Foreign matters to be removed
Suitable frequency to be selected To be changed into thermal type.
Distortion factor to be decreased by reactor Selection of rating to be changed
To be measured with a measuring instrument
Retighten
Reassemble the stud
Groove to be provided
To be replaced by a unit with lower rating
Suitable frequency to be selected
Instantaneous electromagnetic switch to be lowered
Raise the electromagnetic setting of backup breaker or change the rating
Battery to be replaced.
To be returned for repairing.
Selection of rating to be changed