ABB Relion 670 Series Product Manual page 58

Generator protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Generator protection REG670
Version 2.2
Table 17. IOM - Binary input/output module
Quantity
Binary inputs
DC voltage, RL
Power consumption
24/30 V, 50 mA
48/60 V, 50 mA
110/125 V, 50 mA
220/250 V, 50 mA
220/250 V, 110 mA
Counter input frequency
Oscillating signal discriminator
*Debounce filter
Binary input operate time
(Debounce filter set to 0 ms)
* Note: For compliance with surge immunity a debounce filter time setting of 5 ms is required.
58
Rated value
8
24/30 V
48/60 V
110/125 V
220/250 V
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
max. 0.5 W/input
10 pulses/s max
Blocking settable 1-40 Hz
Release settable 1-30 Hz
Settable 1-20 ms
3 ms
© Copyright 2017 Hitachi Power Grids. All rights reserved
Nominal range
-
RL ±20%
RL ±20%
RL ±20%
RL ±20%
-
-
1MRK 502 074-BEN M
Hitachi Power Grids

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents