Huawei SUN2000-2KTL-L1 User Manual page 75

Hide thumbs Also See for SUN2000-2KTL-L1:
Table of Contents

Advertisement

SUN2000-(2KTL-6KTL)-L1
User Manual
Parameter Name
Grid connection
with limited power
(kW)
Issue 04 (2021-04-01)
Communication
disconnection
detection time
Closed-loop controller
Limitation mode
Maximum grid feed-in
power
Power adjustment
period
Power control
hysteresis
Active power output
limit for fail-safe
Communication
disconnection fail-safe
Copyright © Huawei Technologies Co., Ltd.
7 Man-Machine Interaction
Description
Specifies the time for determining the
communication disconnection
between the SUN2000 and the
Dongle.
This parameter is displayed when
Communication disconnection fail-
safe is set to Enable.
● If multiple SUN2000s are
cascaded, set this parameter to
SDongle/SmartLogger.
● If there is only one SUN2000, set
this parameter to Inverter.
Total power indicates export
limitation of the total power at the
grid-tied point.
Specifies the maximum active power
transmitted from the grid-tied point
to the power grid.
Specifies the shortest interval for a
single anti-backfeeding adjustment.
Specifies the dead zone for adjusting
the SUN2000 output power. If the
power fluctuation is within the power
control hysteresis, the power is not
adjusted.
Specifies the derating value of the
SUN2000 active power by percentage.
If the Smart Dongle does not detect
any meter data or the
communication between the Smart
Dongle and the SUN2000 is
disconnected, the Smart Dongle
delivers the derating value of the
SUN2000 active power by percentage.
In the SUN2000 anti-backfeeding
scenario, if this parameter is set to
Enable, the SUN2000 will derate
according to the active power
derating percentage when the
communication between the
SUN2000 and the Smart Dongle is
disconnected for a period longer than
Communication disconnection
detection time.
69

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents