Mitsubishi Electric MELSEC-A Series Manual page 234

Network modules
Hide thumbs Also See for MELSEC-A Series:
Table of Contents

Advertisement

6
REPLACEMENT OF CC-LINK
(2) QnA/QnAS series
The following table shows SB/SW that have different applications on the QnA/QnAS series and the Q
series.
(a) Link special relay (SB)
Number
SB0001
SB0003
SB0007
SB000B
SB000C
SB000D
SB0030
SB0031
SB0032
SB0033
SB0046
SB0057
SB0058
SB005A
SB005B
SB005C
SB005D
SB005E
SB005F
6
- 21
Name
AJ61QBT11/A1SJ61QBT11
Master station switching data
link start
-
Communication command (1)
acceptance
Communication command (1)
complete
Communication command (2)
acceptance
Communication command (2)
complete
-
: Compatible,
QJ61BT11N
Refresh instruction at standby
master switching
Refresh instruction when
changing parameters by the
dedicated instruction
Master station duplication error
canceling request
Transmission speed test
request
Forced master switching
Remote device station
initialization procedure
registration instruction
-
Forced master switching
executable status
Master station duplication error
canceling acknowledgement
Master station duplication error
canceling complete
Master switching request
acknowledgement
Master switching request
complete
Forced master switching
request acknowledgement
Forced master switching
request complete
Execution status of remote
device station initialization
procedure
Completion status of remote
device station initialization
procedure
: Partial change required, × : Incompatible
Compat-
Precautions for replacement
ibility
The specifications of A/AnS
series and Q series are the
same.
Added on the Q series and
replacement is not applied.
Not used on the Q series.
Delete the sequence program
of the section corresponding to
the function, and replace
READ, WRITE instructions with
RIRD, RIWT instructions.
Added on the Q series and
replacement is not applied.
(To next page)