[Design Precautions]
● For the operating status of each station after a communication failure in the data link or the network,
refer to the following manuals.
Failure to do so may result in an accident due to an incorrect output or malfunction.
• Q Corresponding MELSECNET/H Network System Reference Manual (PLC to PLC network)
• Q Corresponding MELSECNET/H Network System Reference Manual (Remote I/O network)
• Q Corresponding MELSECNET/H Remote I/O Module Reference Manual (MELSECNET/10
Mode)
• CC-Link System Master/Local Module User's Manual
● If a coaxial cable is disconnected, the network may be unstable, resulting in a communication failure
of multiple stations. Configure an interlock circuit in the program to ensure that the entire system will
always operate safely even if communications fail. Failure to do so may result in an accident due to
an incorrect output or malfunction.
● When connecting a peripheral with the CPU module or connecting a personal computer with an
intelligent function module to modify data of a running programmable controller, configure an
interlock circuit in the program to ensure that the entire system will always operate safely.
For other forms of control (such as program modification or operating status change) of a running
programmable controller, read the relevant manuals carefully and ensure that the operation is safe
before proceeding. Especially, when a remote programmable controller is controlled by an external
device, immediate action cannot be taken if a problem occurs in the programmable controller due to
a communication failure. To prevent this, configure an interlock circuit in the program, and determine
corrective actions to be taken between the external device and CPU module in case of a
communication failure.
● Do not write any data to the "system area" of the buffer memory in each intelligent function module.
Do not write any data to the "system area" of the buffer memory in the intelligent function module.
Also, do not use any "use prohibited" signals as an output signal from the CPU module to the
intelligent function module. Doing so may cause malfunction of the programmable controller system.
● To set the auto refresh parameter, select the device Y for the remote output (RY) refresh device.
If a device other than Y is selected, the CPU module holds the device status even after its status is
changed to STOP. For how to stop data link, refer to the following manual.
• CC-Link System Master/Local Module User's Manual
● If a CC-Link dedicated cable is disconnected, the network may be unstable, resulting in a
communication failure of multiple stations. Configure an interlock circuit in the program to ensure
that the entire system will always operate safely even if communications fail.
Failure to do so may result in an accident due to an incorrect output or malfunction.
A
- 2
WARNING