Performance Specifications - Mitsubishi Electric MELSEQ FX3S Series User Manual

Hide thumbs Also See for MELSEQ FX3S Series:
Table of Contents

Advertisement

FX
Series Programmable Controllers
3S
User's Manual - Hardware Edition
4.5

Performance Specifications

The performance specifications for the main unit are explained below.
Operation control system
Input/output control system
Programming language
Program memory
Real-time clock
Kinds of instructions
Processing speed
Number
of
input/
output points
Input/output relay
Auxiliary relay
State
Timer
(on-delay timer)
Variable analog potentiometers
Analog inputs
Counter
34
4 Specifications, External Dimensions and Terminal Layout (Main Units)
Item
Built-in memory capacity/type
Memory cassette (Option)
Writing function during running
Keyword function
*1
Clock function
Basic instructions
Applied instructions
Basic instructions
Applied instructions
Input points
Output points
Input relay
Output relay
For general
EEPROM keep
For general
For special
For initial state
(EEPROM keep)
EEPROM keep
For general
100 ms
100 ms/10 ms
1 ms
1 ms accumulating type
100 ms accumulating type
16 bits up (For general)
16 bits up (EEPROM keep)
32 bits up/down (For general)
Stored program repetitive operation system with interruption function.
Batch processing system (when END instruction is executed)
Input/output refresh instruction and pulse catch function are provided.
Relay symbol system + step-ladder system (SFC notation possible)
16,000 steps/EEPROM memory (Program capacity is 4000 steps.)
Max. allowable write: 20,000 times
32,000 steps/EEPROM memory (with loader function)
The FX
Series PLC is available only to 16,000 steps. (Program capacity is 4000
3S
steps.)
Max. allowable write: 10,000 times
Provided (Program can be modified while the PLC is running.)
For the writing function during running, refer to Subsection 5.2.5
With keyword/Customer keyword function
Built-in
1980 to 2079 (with correction for leap year)
2- or 4-digit year, accuracy within 45 seconds/month at 25 °C
Sequence instructions: 29
Step-ladder instructions: 2
116 kinds
0.21 μs/instruction
0.5 μs to several hundred μs/instruction
16 points or less (Extension is impossible.)
14 points or less (Extension is impossible.)
X000 to X017
The device numbers are octal.
Y000 to Y015
M0 to M383
384 points
M384 to M511
128 points
M512 to M1535
1024 points
M8000 to M8511
512 points
S0 to S9
10 points
S10 to S127
118 points
S128 to S255
128 points
T0 to T31
32 points
T32 to T62
31 points
T63 to T127
65 points
T128 to T131
4 points
T132 to T137
6 points
Available as analog timers
VR1: D8030
VR2: D8031
Available as voltage inputs
ch1: D8270
ch2: D8271
C0 to C15
16 points
C16 to C31
16 points
C200 to C234
35 points
4.5 Performance Specifications
Performance
0.1 to 3,276.7 sec
0.1 to 3,276.7 sec/0.01 to 327.67 sec
When M8028 is driven ON, timers T32 to
T62 (31 points) are changed to 10 ms
resolution.
0.001 to 32.767 sec
0.001 to 32.767 sec
0.1 to 3,276.7 sec
→ For compatible PLCs, refer to Chapter 11.
→ For compatible PLCs, refer to Chapter 11.
Counting from 0 to 32,767
Counting from 0 to 32,767
Counting from -2,147,483,648 to
+2,147,483,647
.

Advertisement

Table of Contents
loading

Table of Contents