Step-1 Initial setting for air conditioning system

Make the setting for the BAC-HD150 system and BACnet
Step-1
BAC-HD150
Connect BAC-HD150
(LAN2 port) to the Setting
Tool via a HUB2.
HUB2
Setting Tool
24VDC
PAC-SC51KUA
AG-150A
(1) Installing the Setting Tool software
Install the Setting Tool program on a PC, and set the IP address. (Refer to the Instruction Book that came with Setting Tool for
installation and setting method.)
(2) Disconnecting the BACnet
Disconnect the LAN1 cable that is connected to BAC-HD150 from BACnet
(3) Connecting the Setting Tool
Use additional HUB2 to connect BAC-HD150 and Setting Tool.
Disconnect the cable that is connected to LAN2 port of BAC-HD150 from HUB1, and connect it to the additional HUB2.
HUB
®
BACnet
Disconnect the cable that
®
BACnet
connects BAC-HD150 and
the HUB.
HUB1
LAN1
LAN2
PAC-YG50ECA
LAN
PAC-YG50ECA
PAC-YG50ECA
®
®
related items by using Setting Tool.