Figure 63: Single Line Diagram, The Earthing Switch Is Closed - ABB UniGear Digital Commissioning And Testing Manual

Hide thumbs Also See for UniGear Digital:
Table of Contents

Advertisement

AP PAR ATU S CO NTR O L T E S TI NG
Step 3/7
Check that the earthing switch cannot be closed when the circuit breaker is out of the test
position.
Step 4/7
Move the circuit breaker truck back into the test position. Check the circuit breaker truck sta-
tus on the protection relay LHMI.
Step 5/7
Check that the cable compartment door cannot be open if the earthing switch is open.
Step 6/7
Close the earthing switch and open the cable compartment door. Check the earthing switch
status on the protection relay LHMI.

Figure 63: Single line diagram, the earthing switch is closed

Step 7/7
Check that the earthing switch cannot be open if the cable compartment door is open.
1 VLG 500 0 17 C
PA N E L I NT ER N A L I NT ER LO C KI NG
43