Huawei NetCol5000 C030H6B20 10020E1 Quick Manual page 8

In-row chilled water smart cooling product
Table of Contents

Advertisement

3.7
Combining Cabinets from Front and Rear Door
1. Do not remove anchor bolts.
Otherwise, you need to
rework them for use.
2. Level the cabinet with the
help of a measuring tape.
Check that the vertical
distance between the top of
the cabinet and the floor is
2000 mm (tolerance±3
mm) and that the cabinet is
leveled horizontally.
3. Wrench an anchor bolt
clockwise to elevate the
cabinet, or wrench an
anchor bolt anticlockwise to
lower it. A cabinet leg can
be adjusted within a range
of 0–8 mm.
(Optional) Removing the
3.8
Transport Fixing Metals
This step applies to the model with 1100
mm and 1200 mm depth, and electric
heater or water pump.
(Optional) Relocating the Baffle
3.9
Plate
Perform the following procedures to change the
supply air direction if required.
8