Download Print this page

Huawei FusionDC1000A Quick Manual page 40

Prefabricated all-in-one data center
Hide thumbs Also See for FusionDC1000A:

Advertisement

Category
Battery Settings
Setting
iBOX Setting
Dry contact
User Settings
Parameter
Dis. cur. 0.1CEOD (V/cell)
Dis. cur. 0.3CEOD (V/cell)
Dis. cur. 0.5CEOD (V/cell)
Dis. cur. 1.0CEOD (V/cell)
Sched. shallow dis. test
Sched. shallow dis. test time
Sched. shallow dis. test interval (d)
Shallow dis.test dis. ratio
(%)
Cell charge voltage (V/cell)
Chg. cur.
Lithium battery
limiting coef. (C)
Number of iBOXs
Start address for iBOX-
iBOX Setting
NMS
iBOX number of iBATs
Current source
Batt. abnormal
Advanced Param
BCB trip
Multi-Hall cur. Setting
BCB connection
Batter breaker
Language
Password
password
complexity
Default Value
Value Range
1.8
1.8–1.9
1.8
1.8–1.9
1.75
1.75–1.85
1.6
1.6–1.75
Disable
Enable/Disable
00:00-06:00, 06:00-12:00,
00:00 - 06:00
12:00-18:00, 18:00-24:00
60
30–90
20
10–50
-
0.5
0.10–1.00
0
0
0–124
0
0–300
Hall sensor 200A, Hall
200A
sensor 600A
Disable
Disable, Enable
1
Disable
Enable/Disable
Disable
Enable/Disable
12 languages, including
English
English, Chinese, Italian,
000001
Enable
Enable/Disable
Setting
1.8
1.8
1.75
1.6
Disable
00:00-06:00
60
20
-
-
0.5
0–6
Default value
Default value
Default value
Default value
Default value
1–8
Default value
Default value
Default value
English
/
Default value
Enable
Remarks

Advertisement

loading