Download Print this page

ABB TPU-2000R Manual page 4

Transformer protection unit
Hide thumbs Also See for TPU-2000R:

Advertisement

ABB Transformer Protection Unit 2000R
WARNING:
Interrupting the download process before it is completed will result in lost EEPROM data. In the
event that the download is prematurely terminated, contact the factory.
To download new software to the TPU-2000R:
If desired, save all settings to a disk as described in Section 12.
On your computer's hard drive, create a directory called C:\FPI.
Copy files from the FPI diskette (FPI.exe) and the SAF diskette ( filename .abs) to the C:\FPI drive.
Remember the filename from the SAF diskette as it will be needed later.
Connect the TPU-2000R to the computer via the serial port on the front panel of the unit with a null modem
cable.
Ensure that the communications settings of the computer com port and the settings of the TPU-2000R are
both set to 9600, 8, N, 1.
At the C:\FPI prompt, type FPI
At the Monitor Type ? prompt, select the appropriate monitor (color or black and white) and press <CR>.
After the ABB description screen, the Communication Options screen appears. Use the spacebar to change
the com settings or accept the default settings by scrolling through the screen with the <CR> key.
If all com settings are correct, the Successful Connection To... screen appears. Press <CR> to continue. The
next screen to appear will be the Main Menu. If com settings are not compatible or some other problem
exists, the Communication Status screen appears. Reset the com settings and recheck connections and
press <CR>.
The only option necessary for downloading the software update is the Update Unit Software selection. Using
the arrow keys, scroll to the Update Unit Software selection and press <CR>.
At the warning message screen, select continue with unit software update.
At the Load New Firmware Data screen, type filename .abs ( filename is the name of the file) copied from the
SAF disk) and press <CR>. This will highlight the default action, [READ FROM DISK]. Press <CR> again.
Downloading should take about 20 minutes to complete.
During download, the TARGET LEDs on the front panel will blink intermittently and in sequence starting with
ØA with the following notes:
Computer display
Monitor Has Been Entered
Flash Erase
Flash Programming
The message "Successfully Completed Downloading! Hit Any Key To Return To Main Menu" will appear.
Hitting the <CR> key will cause the systems to reboot and the message "Please Wait While System Reboots"
will appear.
After the system has rebooted, the Main Menu will reappear. Scroll down to the Quit Program selection and
press <CR>.
Restore settings to the relay as described in Section 12.
4-8
LED
ØA blinks
ØB blinks
ØC blinks
MMI (If present)
TPU2000R Monitor
Flash Memory Erase in Progress
Flash Memory Download in Progress
Relay Design and Specifications