Acs880 Multidrives - ABB Q951 User Manual

Emergency stop functions with button monitoring foracs880 liquid-cooled drives
Hide thumbs Also See for Q951:
Table of Contents

Advertisement

36 Description of option +Q952+Q984

ACS880 multidrives

The parameter settings in the ACS880 primary control program:
No.
Name
10.24
RO1 source
21.04
Emergency
stop mode
21.05
Emergency
stop source
1) Value set by ABB at the factory for the default design.
2) Delivery-specific. Refer to the circuit diagrams.
The table that follows gives the parameters in the ACS880 primary control program that you
must set according to application requirements. Make sure that the selected values agree
with the time delay settings of the emergency stop safety relay [A61]. Refer to
settings (page
37).
No.
Name
21.06
Zero speed lim-
it
23.23
Emergency
stop time
46.01
Speed scaling
46.02
Frequency
scaling
The table that follows gives the parameters related to the safety function in the ACS880
supply control programs. The parameters are set at the factory.
No.
Name
121.04
Emergency
stop mode
121.05
Emergency
stop source
1) Value set by ABB at the factory for the default design.
For more information, see the firmware manuals.
1)
Description
Default value
2)
Selects a drive signal to be connected to relay output RO1.
P.10.1.3 -
In this case, the source is the inverted value of parameter
10.01 DI status bit 3 (DI4).
Eme ramp stop (Off3)
Selects the way the motor is stopped when an emergency
stop command is received.
2)
Selects the source of the emergency stop signal.
DI4
Value
Description
User-defined
Defines the zero speed limit. The motor is stopped along a
speed ramp until this limit is reached. After the zero speed
delay (parameter 21.07, default value 0 ms), the motor coasts
to a stop.
User-defined
Defines the deceleration time for emergency stop Off3. The
deceleration time is the time it takes to decelerate the motor
from the maximum process speed defined by parameter
46.01 or 46.02 to the zero speed limit defined by parameter
21.06.
User-defined
Defines the maximum motor speed used in the application.
Set this parameter if you use the speed control mode or
torque control mode.
User-defined
Defines the maximum motor frequency used in the applica-
tion. Set this parameter if you use the frequency control
mode.
1)
Description
Default value
Stop and warning
Selects the way the supply unit is stopped when an emer-
gency stop command is received.
DIIL
Selects the source of the emergency stop signal. This para-
meter cannot be changed while the supply unit is running.
Hardware

Advertisement

Table of Contents
loading

This manual is also suitable for:

Q984Q952

Table of Contents