Resetting The Safety Function - ABB Q951 User Manual

Emergency stop functions with button monitoring foracs880 liquid-cooled drives
Hide thumbs Also See for Q951:
Table of Contents

Advertisement

42 Use of the safety function

Resetting the safety function

WARNING!
Make sure that the drive does not start accidentally. This can occur after the reset
of the safety function, if a level-triggered start command and the start enable signal
are on at the same time.
1. Return the emergency stop button [S61] or user-defined push button to the normal
position. For example, turn the emergency stop button [S61] until it releases.
2. Push the emergency stop reset button [S62] on the cabinet door for 0.1 ... 3 seconds.
The emergency stop reset button indicator light [S62] goes off, and the emergency stop
is deactivated.
3. If necessary, reset faults from the drive.
4. If necessary, close the main contactor/breaker.
5. Make sure that the drive receives the start signal.
6. You can now restart the drive.
For more information, see the hardware and firmware manuals.
Note: You must also reset the emergency stop safety relay [A61] or [A640] with the
emergency stop reset button [S62] each time after you energize the relay. If you do not
reset the relay, you cannot close the main contactor/breaker.