Component
UPS-1/2
Parameter
Category
Language
Basic
Password
Single/Parallel
Output voltage level
Output frequency
Basic Param.
Battery capacity
Number of cells
System capacity
Requisite modules
Advanced
Param.
Redundant modules
BSC mode
Maximum bypass
Bypass Param.
voltage
BCB connection
Dry Contacts
Batter breaker
Battery Param.
Installation time
Integrated UPS (25 kVA-125 kVA) Initial Configuration Parameters
Default
Value
English
1
Single
400 V
50Hz
40 kVA
100Ah
80 kVA
100Ah
120/128 kVA
100Ah
192
/
/
/
Non-BSC
voltage level is 380 V
+15%
voltage level is 400 V
+15%
voltage level is 415 V
+10%
Disable
Disable
/
Value Range
12 languages, including English,
Chinese, Italian, and so on
/
Single, Parallel
380 V, 400 V, 415 V
50 Hz, 60 Hz
5Ah–3000Ah
180–240
/
/
/
Master BSC mode, Non-BSC
mode, Slave BSC mode
+10%, +15%, +20%, +25%
+10%, +15%, +20%
+10%, +15%
Disable/Enable
Disable/Enable
/
Setting
English
Default value
Single
380 V
50 Hz
27Ah
240
75kVA
3
0
Non-BSC
Default value
Default value
Default value
Disable
Disable
Set by service personnel
Remarks