Category
Parameter
PDU Parameters-Branch breaker open alarm
enable
PDU Parameters-Branch breaker open alarm
enable
Settings
PDU Parameters-Branch breaker open alarm
enable
PDU Parameters-Main input 3-phase cur. Imb
Default
Value Range
Value
Enable
Disable/Enable/User-defined
Enable
Disable/Enable/User-defined
Enable
Disable/Enable/User-defined
Enable
Disable/Enable/User-defined
Setting
User-defined (After setting the parameter to User-defined, disable the spare
branch circuit breaker in the Installation time PDU > Branch Battery conceptual
diagram and enable the branch circuit breaker that connects to a load.)
User-defined (After setting the parameter to User-defined, disable the spare
branch circuit breaker in the Installation time PDU > Branch Battery conceptual
diagram and enable the branch circuit breaker that connects to a load.)
User-defined (After setting the parameter to User-defined, disable the spare
branch circuit breaker in the Installation time PDU > Branch Battery conceptual
diagram and enable the branch circuit breaker that connects to a load.)
Disable
Remarks