No.F002 Fire Extinguishing System Conceptual Diagram (CE) -3
red
-
+
+
ROV
SIL
AL
E
AUX
REMOTE
24V
CONTROL
Technical requirements:
1.
All fire extinguishing signal cables are red (BOM number: 25033402-005) and black (BOM number: 25033402) cables
diagram.
2. Connect the Smoke Detector,Heat Detector,Horn Storbes,Fire Alarm Bell and Start/Stop Button to the UT terminal (14170025). Cord end terminals (14170214) are used to connect other fire devices and extinguishing control panels host terminals.
3. Connect a 10K terminal resistor to each of the last the fire alarm sounder and fire alarm horn/strobe in parallel.
4. Connect cables to the smoke detector and heat detector by referring to the diagram. Connect a 6.8 K terminal resistor to the last smoke and heat detectors in parallel.
5. Connect the emergency abort button and pneumatic switch to a 6.8 K terminal resistor in parallel, and to a 470 ohm resistor in serial. Connect an electrical actuator to a 1N4004 diode in parallel.
6. Alarm signals are reported to the monitoring system over shielded straight-through network cables. The connection definitions are as follows: LOCAL FIRE, FIRE RELAY, and FAULT RELAY. The signal cables connect to the ECC over dry contacts.
7. Attach cable labels to all cables connected to the extinguishant control panel and wiring terminals on electrical actuators and pneumatic switches. See the label table for the label content. Cable direction labels must be arranged neatly in the same direction. Cables must be bound neatly, with cable ties in the same
direction. (Labels are printed on label paper with the BOM number 29041061, attached on cable ties with the BOM number 21200708, and bound to corresponding cables.)
AC PDB-1
4
3
Relay
2
AC PDB-1
QF7
5
1
DC24V-
DC24V+
black
+
-
+
-
+
-
+
-
+
-
+
-
+
FLT
RST
DATA
POWER
ZONE 1
ZONE 2
ZONE 3
S1
S2
STATUS UNITS
Connect the
Connect smoke
Connect heat
Data cable
Power cable
first stage
detector in
detector in
alarm to the
detection zone 1
detection zone 2
fire alarm
bell.
The red cable is positive and the black cable is negative. The pneumatic switch, Warning signs, and fire alarm bell each has two wiring terminals that connect to two wires. The fire alarm bell is polarity insensitive. For details, see the
black
-
+
-
+
-
+
-
+
-
NC
C
NO
NC
C
NO
2ND
1ST
2ND
MODE
MAN
HOLD
SELECT
RELEASE
SOUNDER
STAGE
STAGE
SWITCH
Connect the
Connect the
second stage alarm
emergency
to the horn strobes
abort port to
and warning signs .
the
Extinguishant
abort button.
+
-
+
-
+
-
NO
C
NC
C
NO
NC
C
NO
NC
C
REL
LOW
FAULT
LOCAL
FIRE
EXTING
EXTRACT
PRESS
PRESS
RELAY
FIRE
RELAY
SWITCH
Connect the
Connect the
Connect the fault
Connect the gas release
Connect the fire alarm
pressure
electrical
signal output (NO) to
signal output (NO) to
signal output (NO) to
actuator drive
the collector of the
the collector of the
the collector of the
signal to the
signal to the
monitoring system.
monitoring system.
monitoring system.
pneumatic
electrical
switch.
actuator.