Product Overview
Item
Cabinet dimensions (H x W x D)
(unit: mm)
Installation scenario
Installation space
Power distribution
Operating temperature
Operating humidity
IP rating
Maximum power of a single cabinet
Installation mode
Altitude
•
The component layout is only for reference. The actual installation positions prevail.
•
If the IVS, server, and LAN switch are configured, determine their installation positions
based on the site requirements.
Converged Cabinet: 2000 x 600 x 1100
Supports only a single cabinet.
The cabinet provides 42 U available space. The mounting
bars are adjustable. The installation position for horizontal
rPDUs is set at the rear of the cabinet.
6 kVA UPS
rPDU: horizontally installed; options: IEC and GB
Lithium battery: 100 Ah/48 V DC
Indoor: 0°C to 40°C
5%–95% RH
IP20
3 kW
Installed on a concrete floor or an electrostatic discharge
(ESD) floor
≤ 1000 m (derated when the altitude ranges from 1000 m
to 4000 m)
Copyright © Huawei Technologies Co., Ltd. 2021.
1
All rights reserved.
Specifications
Components to Be
Installed Onsite
Lithium battery
Water sensor
Temperature and humidity
(T/H) sensor
rPDU
LAN Switch (Optional)
Server (Optional)
IVS (Optional)
Camera (Optional)