Product Overview - Huawei FusionModule500 Quick Manual

Smart mini data center
Hide thumbs Also See for FusionModule500:
Table of Contents

Advertisement

Product Overview

Item
Cabinet dimensions (H x W x D)
(unit: mm)
Installation scenario
Installation space
Power distribution
Operating temperature
Operating humidity
IP rating
Maximum power of a single cabinet
Installation mode
Altitude
The component layout is only for reference. The actual installation positions prevail.
If the IVS, server, and LAN switch are configured, determine their installation positions
based on the site requirements.
Converged Cabinet: 2000 x 600 x 1100
Supports only a single cabinet.
The cabinet provides 42 U available space. The mounting
bars are adjustable. The installation position for horizontal
rPDUs is set at the rear of the cabinet.
6 kVA UPS
rPDU: horizontally installed; options: IEC and GB
Lithium battery: 100 Ah/48 V DC
Indoor: 0°C to 40°C
5%–95% RH
IP20
3 kW
Installed on a concrete floor or an electrostatic discharge
(ESD) floor
≤ 1000 m (derated when the altitude ranges from 1000 m
to 4000 m)
Copyright © Huawei Technologies Co., Ltd. 2021.
1
All rights reserved.
Specifications
Components to Be
Installed Onsite
Lithium battery
Water sensor
Temperature and humidity
(T/H) sensor
rPDU
LAN Switch (Optional)
Server (Optional)
IVS (Optional)
Camera (Optional)