5.1.4 Cable connections

The coaxial cable connections between CPUs are shown in figure 5.3.
As shown in figure 5.3, the TXD is connected to the opposing RXD to ensure that only one cable is sued for
the entire link system. The maximum length of the coaxial cable between stations is 500m. The overall length
of the cable (the total length of the cable between each station) is 1,000m

5.1.5 Using the insulated cable connector tube

Ensure that the insulated cable connector tube supplied covers the entire BNC connector.
Insulated cable
connector tube
Figure 5.4 External view of the insulation tube covering the coaxial connector
Note: If the BNC connector in use is not the recommended model and has a larger diameter preventing it from
being inserted into the insulation tube, cut the tube as shown below.
Secure the insulation tube in place from the top with insulation tape to prevent it from
falling of.
ST0
TxD
RxD
ST1
TxD
RxD
Figure 5.3 Coaxial cable connection diagram
5-3
Chapter 5. Installation and start-up
RxD
TxD
Cut in a straight line.
ST3
TxD
ST2
RxD