Section 2 Dnp3 Data Mappings; Overview - ABB Relion 615 Series Manual

Transformer protection and control
Hide thumbs Also See for Relion 615 Series:
Table of Contents

Advertisement

1MRS756881 B
Section 2
2.1
RET615
Point List Manual
DNP3 data mappings

Overview

This document describes the DNP3 data points and structures available in RET615
Ver. 3.0. The data points are unmapped as a default.The point lists describe a
superset of all data available through the standard configurations A, B, C, D, E, F,
G, and H including the optional functionalities. The names of the standard
configurations are TE01, TE02, TE03, TE04, TE05, TE06, TE07 and TE08
respectively.
The point tables show all the available DNP3 data points in this IED. The data
objects in the point tables are listed in alphabetical order based on the objects'
IEC61850 names. The DNP3 points can be freely added, removed, reorganized and
reconfigured using PCM600.
As a default, the class assignments are Class 0 and Class 1 for binary inputs and
Class 0 and Class 2 for analog inputs. Analog values are provided with default
scalings. The scalings can be freely modified by the user.
This list represents the superset of DNP3 points. The actual set of available points
is determined by the IED's ordercode.