ABB RELION 615 SERIES Product Manual

Voltage protection and control
Hide thumbs Also See for RELION 615 SERIES:

Advertisement

RELION® 615 SERIES
Voltage Protection and Control
REU615
Product Guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB RELION 615 SERIES

  • Page 1 — RELION® 615 SERIES Voltage Protection and Control REU615 Product Guide...
  • Page 2: Table Of Contents

    16. Access control............14 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. © Copyright 2018 ABB.
  • Page 3: Description

    REU615 is a creation of multi-layer logic functions using various logical ® member of ABB’s Relion product family and part of its 615 elements, including timers and flip-flops. By combining protection and control product series. The 615 series relays are...
  • Page 4 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 REU615 VOLTAGE PROTECTION AND CONTROL RELAY STANDARD CONFIGURATION PROTECTION LOCAL HMI ALSO AVAILABLE - Disturbance and fault recorders 2× - Event log and recorded data Master Trip - High-Speed Output module (optional) Configuration System Lockout relay...
  • Page 5 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 REU615 VOLTAGE PROTECTION AND CONTROL RELAY STANDARD Automatic voltage regulator CONFIGURATION PROTECTION LOCAL HMI ALSO AVAILABLE - Disturbance and fault recorders 2× - Event log and recorded data Master Trip - Local/Remote push button on LHMI Configuration System...
  • Page 6 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 Table 2. Supported functions Function IEC 61850 Protection Three-phase non-directional overcurrent protection, low stage PHLPTOC Three-phase non-directional overcurrent protection, high stage PHHPTOC Three-phase non-directional overcurrent protection, instantaneous stage PHIPTOC Residual overvoltage protection ROVPTOV Three-phase undervoltage protection...
  • Page 7: Protection Functions

    Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 Table 2. Supported functions, continued Function IEC 61850 Analog value scaling (4 pcs) SCA4GAPC Integer value move (4 pcs) MVI4GAPC 1, 2, ... = Number of included instances. The instances of a protection function represent the number of identical protection function blocks available in the standard configuration.
  • Page 8 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 can be used for load-side voltage regulation. For substations the master/follower principle, the negative reactance principle with two or more power transformers operating in parallel, three (NRP) and the minimizing circulating current (MCC) principle. alternative voltage regulation principles are available, that is, REF615 Std.
  • Page 9: Supported Abb Solutions

    To facilitate the system engineering, ABB's receiving of sampled values of voltages is supported. relays are supplied with connectivity packages. The...
  • Page 10 The collected network supervision. Table 3. Supported ABB solutions Product Version Substation Management Unit COM600S 4.0 SP1 or later 4.1 or later (Edition 2)
  • Page 11: Control

    GOOSE communication GUID-4D002AA0-E35D-4D3F-A157-01F1A3044DDB V4 EN Figure 5. ABB power system example using Relion relays, COM600S and MicroSCADA Pro/System 800xA 6. Control configuration can be modified to release some binary inputs or REU615 integrates functionality for the control of a circuit outputs which have originally been configured for other breaker via the front panel HMI or by means of remote controls.
  • Page 12: Measurements

    Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 application are configured using the signal matrix or the can be set to record either the waveform or the trend of the application configuration functionality of PCM600. currents and voltages measured. Standard configuration A incorporates a synchrocheck function The analog channels can be set to trigger the recording function to ensure that the voltage, phase angle and frequency on either...
  • Page 13: Condition Monitoring

    Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 PROCESS LEVEL USER LEVEL Process events 1024 (FIFO) Fault records (FIFO) Fault summary; Trip timestamp, Function, Currents, Voltages, etc. Audit trail events (FIFO) 2048 System and security-related events; Configuration changes, Control, Login, etc. Disturbance records n…100...
  • Page 14: Fuse Failure Supervision

    Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 14. Fuse failure supervision The residual current input and the phase-current inputs are The fuse failure supervision detects failures between the rated 1/5 A. The three phase-voltage inputs and the residual- voltage measurement circuit and the relay.
  • Page 15: Station Communication

    Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 18. Station communication The relay also supports IEC 61850 process bus by sending The relay supports a range of communication protocols sampled values of analog currents and voltages and by including IEC 61850 Edition 2, IEC 61850-9-2 LE, IEC receiving sampled values of voltages.
  • Page 16 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 COM600 SCADA Ethernet switch Ethernet switch IEC 61850 PRP GUID-334D26B1-C3BD-47B6-BD9D-2301190A5E9D V2 EN Figure 7. Parallel redundancy protocol (PRP) solution HSR applies the PRP principle of parallel operation to a single sender node discards the frame to avoid loops.
  • Page 17 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 COM600 Devices not supporting HSR SCADA Ethernet switch Redundancy Redundancy Redundancy IEC 61850 HSR REF620 RET620 REM620 REF615 REF615 GUID-7996332D-7FC8-49F3-A4FE-FB4ABB730405 V1 EN Figure 8. High availability seamless redundancy (HSR) solution The choice between the HSR and PRP redundancy protocols switch-over.
  • Page 18 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 Client A Client B Network A Network B Managed Ethernet switch Managed Ethernet switch with RSTP support with RSTP support GUID-AB81C355-EF5D-4658-8AE0-01DC076E519C V4 EN Figure 9. Self-healing Ethernet ring solution All communication connectors, except for the front port records are supported.
  • Page 19 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 The relay supports the following high accuracy time • Layer 2 mapping synchronization method with a time-stamping resolution of 4 µs • Peer to peer delay calculation required especially in process bus applications. •...
  • Page 20: Technical Data

    Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 19. Technical data Table 6. Dimensions Description Value Width Frame 177 mm Case 164 mm Height Frame 177 mm (4U) Case 160 mm Depth 201 mm (153 + 48 mm) Weight Complete protection relay 4.1 kg...
  • Page 21 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 Table 9. Binary inputs Description Value Operating range ±20% of the rated voltage Rated voltage 24...250 V DC Current drain 1.6...1.9 mA Power consumption 31.0...570.0 mW Threshold voltage 16...176 V DC Reaction time <3 ms Table 10.
  • Page 22 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 Table 12. Signal outputs and IRF output Description Value Rated voltage 250 V AC/DC Continuous contact carry Make and carry for 3.0 s 10 A Make and carry 0.5 s 15 A Breaking capacity when the control-circuit time constant L/R<40 ms, at 1 A/0.25 A/0.15 A...
  • Page 23 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 Table 15. High-speed output HSO with BIO0007 Description Value Rated voltage 250 V AC/DC Continuous contact carry Make and carry for 3.0 s 15 A Make and carry for 0.5 s 30 A Breaking capacity when the control-circuit time constant L/R <40 ms, at 5 A/3 A/1 A...
  • Page 24 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 Table 20. Degree of protection of flush-mounted protection relay Description Value Front side IP 54 Rear side, connection terminals IP 20 Table 21. Environmental conditions Description Value Operating temperature range -25...+55ºC (continuous) Short-time service temperature range 1)2)
  • Page 25 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 Table 22. Electromagnetic compatibility tests Description Type test value Reference 1 MHz/100 kHz burst disturbance test IEC 61000-4-18 IEC 60255-26, class III IEEE C37.90.1-2002 • Common mode 2.5 kV •...
  • Page 26 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 Table 22. Electromagnetic compatibility tests, continued Description Type test value Reference Power frequency immunity test Binary inputs only IEC 61000-4-16 IEC 60255-26, class A • Common mode 300 V rms •...
  • Page 27 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 Table 25. Environmental tests Description Type test value Reference Dry heat test • 96 h at +55ºC IEC 60068-2-2 • 16 h at +85ºC Dry cold test • 96 h at -25ºC IEC 60068-2-1 •...
  • Page 28 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 Protection functions Table 29. Three-phase non-directional overcurrent protection (PHxPTOC) Characteristic Value Operation accuracy Depending on the frequency of the measured current: f ±2 Hz PHLPTOC ±1.5% of the set value or ±0.002 × I PHHPTOC ±1.5% of set value or ±0.002 ×...
  • Page 29 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 Table 31. Residual overvoltage protection (ROVPTOV) Characteristic Value Operation accuracy Depending on the frequency of the measured voltage: f ±2 Hz ±1.5% of the set value or ±0.002 × U Minimum Typical Maximum...
  • Page 30 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 Table 34. Three-phase undervoltage protection (PHPTUV) main settings Parameter Function Value (Range) Step Start value PHPTUV 0.05...1.20 × U 0.01 Time multiplier PHPTUV 0.05...15.00 0.01 Operate delay time PHPTUV 60...300000 ms PHPTUV Definite or inverse time...
  • Page 31 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 Table 37. Positive-sequence undervoltage protection (PSPTUV) Characteristic Value Operation accuracy Depending on the frequency of the measured voltage: f ±2 Hz ±1.5% of the set value or ±0.002 × U Minimum Typical Maximum...
  • Page 32 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 Table 41. Frequency protection (FRPFRQ) Characteristic Value Operation accuracy f>/f< ±5 mHz df/dt ±50 mHz/s (in range |df/dt| <5 Hz/s) ±2.0% of the set value (in range 5 Hz/s < |df/dt| < 15 Hz/s) Start time f>/f<...
  • Page 33 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 Table 45. Arc protection (ARCSARC) Characteristic Value Operation accuracy ±3% of the set value or ±0.01 × I Operate time Minimum Typical Maximum Operation mode = "Light only" 9 ms 10 ms 12 ms 4 ms...
  • Page 34 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 Table 50. Load-shedding and restoration (LSHDPFRQ) main settings Parameter Function Value (Range) Step Load shed mode LSHDPFRQ 1 = Freq< 6 = Freq< OR df/dt 8 = Freq< AND df/dt Restore mode LSHDPFRQ 1 = Disabled...
  • Page 35 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 Control functions Table 52. Tap changer position indication (TPOSYLTC) Descrpition Value Response time for binary inputs Typically 100 ms Table 53. Tap changer control with voltage regulator (OLATCC) Characteristic Value Depending on the frequency of the measured current: f ±2 Hz...
  • Page 36 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 Table 54. Tap changer control with voltage regulator (OLATCC) main settings Parameter Function Value (Range) Step Auto parallel mode OLATCC 2 = Auto master 3 = Auto follower 5 = NRP 7 = MCC Band center voltage OLATCC...
  • Page 37 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 Table 55. Synchronism and energizing check (SECRSYN) Characteristic Value Operation accuracy Depending on the frequency of the voltage measured: f ±1 Hz Voltage: ±3.0% of the set value or ±0.01 × U Frequency: ±10 mHz Phase angle:...
  • Page 38 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 Condition and supervision functions Table 57. Current circuit supervision (CCSPVC) Characteristic Value <30 ms Operate time Including the delay of the output contact Table 58. Current circuit supervision (CCSPVC) main settings Parameter Function Value (Range)
  • Page 39 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 Measurement functions Table 61. Three-phase current measurement (CMMXU) Characteristic Value Operation accuracy Depending on the frequency of the measured current: f ±2 Hz ±0.5% or ±0.002 × I (at currents in the range of 0.01...4.00 × I Suppression of harmonics DFT: -50 dB at f = n ×...
  • Page 40 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 Table 66. Three-phase power and energy measurement (PEMMXU) Characteristic Value Operation accuracy At all three currents in range 0.10…1.20 × I At all three voltages in range 0.50…1.15 × U At the frequency f ±1 Hz ±1.5% for apparent power S...
  • Page 41 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 Other functions Table 69. Pulse timer (PTGAPC) Characteristic Value Operate time accuracy ±1.0% of the set value or ±20 ms Table 70. Time delay off (8 pcs) (TOFPAGC) Characteristic Value Operate time accuracy ±1.0% of the set value or ±20 ms...
  • Page 42: Local Hmi

    Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 20. Local HMI default single line diagram. The SLD view can also be accessed The relay is available with two optional displays, a large one and using the Web browser-based user interface. The default SLD a small one.
  • Page 43: Mounting Methods

    (PST), a Next-Generation Order Number circuiting the CT secondary circuits when a relay unit is Tool, supports order code creation for ABB Distribution withdrawn from its case. The relay case is further provided with Automation IEC products with emphasis on, but not exclusively a mechanical coding system preventing the current measuring for, the Relion product family.
  • Page 44: Accessories And Ordering Data

    Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 24. Accessories and ordering data Table 74. Cables Item Order number Optical sensor for arc protection, cable length 1.5 m 1MRS120534-1.5 Optical sensor for arc protection, cable length 3.0 m 1MRS120534-3 Optical sensor for arc protection, cable length 5.0 m 1MRS120534-5...
  • Page 45: Tools

    Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 25. Tools (Internet Explorer). For security reasons, the Web HMI is The protection relay is delivered as a preconfigured unit. The disabled by default but it can be enabled via the local HMI. The default parameter setting values can be changed from the front- Web HMI functionality can be limited to read-only access.
  • Page 46: Cyber Security

    Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 Table 77. Supported functions Function Web HMI PCM600 Relay parameter setting ● ● Saving of relay parameter settings in the relay ● ● Signal monitoring ● ● Disturbance recorder handling ●...
  • Page 47: Terminal Diagrams

    Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 27. Terminal diagrams GUID-B89BFFF3-08F0-40D3-8F12-99FB21B3900F V1 EN Figure 15. Terminal diagram of standard configuration A...
  • Page 48 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 GUID-E5FA44B9-524F-4B19-A002-49D39DF6D6D5 V1 EN Figure 16. Terminal diagram of standard configuration B...
  • Page 49: Certificates

    REU615 Product version: 5.0 FP1 28. Certificates 29. References DNV GL has issued an IEC 61850 Edition 2 Certificate Level A1 www.abb.com/substationautomation portal provides information on the entire range of distribution automation ® for Relion 615 series. Certificate number: 7410570I-OPE/INC products and services.
  • Page 50: Functions, Codes And Symbols

    Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 30. Functions, codes and symbols Table 78. Functions included in the relay Function IEC 61850 IEC 60617 IEC-ANSI Protection Three-phase non-directional overcurrent protection, PHLPTOC1 3I> (1) 51P-1 (1) low stage Three-phase non-directional overcurrent protection, PHHPTOC1 3I>>...
  • Page 51 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 Table 78. Functions included in the relay, continued Function IEC 61850 IEC 60617 IEC-ANSI Multipurpose protection MAPGAPC1 MAP (1) MAP (1) MAPGAPC2 MAP (2) MAP (2) MAPGAPC3 MAP (3) MAP (3) MAPGAPC4 MAP (4)
  • Page 52 Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 Table 78. Functions included in the relay, continued Function IEC 61850 IEC 60617 IEC-ANSI Trip circuit supervision TCSSCBR1 TCS (1) TCM (1) TCSSCBR2 TCS (2) TCM (2) Current circuit supervision CCSPVC1 MCS 3I (1) MCS 3I (1)
  • Page 53: Document Revision History

    Voltage Protection and Control 1MRS757058 K REU615 Product version: 5.0 FP1 Table 78. Functions included in the relay, continued Function IEC 61850 IEC 60617 IEC-ANSI Set-reset (8 pcs) SRGAPC1 SR (1) SR (1) SRGAPC2 SR (2) SR (2) SRGAPC3 SR (3) SR (3) SRGAPC4 SR (4)
  • Page 56 ABB Distribution Solutions Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 ABB Distribution Automation Maneja Works Vadodara-390013, India Phone +91 265 2604386 +91 265 2638922 www.abb.com/mediumvoltage www.abb.com/relion www.abb.com/substationautomation © Copyright 2018 ABB. All rights reserved.