Read Holding Register - Function Code 03 - ABB COMMANDER 100 Operating Manual

Modbus (rtu) communications option
Table of Contents

Advertisement

...5 MODBUS FUNCTIONS
5.2 Read Holding Register – Function Code 03
5.2.1 Read Holding Register Query
The Read Holding Register Query obtains the contents of up to eight holding
registers in the addressed slave.
Note. The data start register must contain the offset address of the first
register to be accessed, e.g. to start at register 1 the data start register must
contain 00 (00H).
Broadcast mode is not supported by Function Code 03.
Example. Read three holding registers from slave (01) starting at holding address
01 (process variable input).
Address Function
01
03
5.2.2 Read Holding Register Response
The addressed slave responds with its address and function code, followed by the
information field. The information field contains one byte describing the quantity of
data bytes to be returned. Two bytes are used to return each register requested,
the first byte containing the high order bits and the second the low order bits.
Example
PV input (two registers) –
PV decimal places
Address Function Count Register 01
01
03
10
Register
Register
Start
Start
Offset High Offset Low
00
00
270
Byte
Holding
High Low
00
00
00
Data No.
of Registers of Registers Check ( C R C - 1 6 )
High
00
1
Holding
Register 02
Register 03
High Low
High Low
01
09
Data No.
Error
Coils Low
Field
03
05
Holding
Error
Check ( C R C - 1 6 )
Field
00
01
49
CB
75