3 CONFIGURATION

Information.
Programmable baud rate – 2400 or 9600 baud.
Selectable parity – odd, even or none.
Address range – 1 to 99.
For MODBUS communications to operate correctly, each slave instrument must
be configured with the correct serial transmission parameters and assigned a
unique address.

3.1 Accessing the Configuration Mode

To access the Configuration Mode, set the security switch to the 'Configure'
position, as shown in Fig. 4.1 of the relevant User Guide. When all parameters have
been programmed, reset the switch to the 'Normal' position.
3.2 Setting the Serial Transmission Parameters – Fig. 3.1
Fig. 3.1 shows the display readouts and options available when defining the serial
transmission rate and bit parity for COMMANDER 100, 150, 160 and V100
instruments. Further detail on the procedure required to set each parameter are
shown in Section 4.3.4 of the relevant User Guide.

3.3 Setting the MODBUS Address

To allow the master to differentiate between more than one slave in a system, each
slave on a MODBUS link must be assigned a unique address in the range 1 to 99.
See Section 4.4 of the relevant User Guide (MODBUS Address Frame,
S – Serial Communication Configuration
C100/V100
PrSt
2100
Display Baud Rate, 2/4-wire
0
Off
1
2400, 2-wire
2
2400, 4-wire
3
9600, 2-wire
4
9600, 4-wire
Fig. 3.1 Setting Serial Transmission Parameters
6
C150/160
S
0000
T – Serial Communications Parity
C100/V100
C150/160
PrSt
t 0000
2100
Display Parity
0
None
1
Odd
2
Even
Addr
).