Location Specifications And Design; Wiring Requirements; Unpack And Inspect; Basic Hardware Installation - ABB RMC-100 Startup Manual

Remote modular controller
Hide thumbs Also See for RMC-100:
Table of Contents

Advertisement

2.4

Location specifications and design

Decide on the location to install the controller. The RMC mounts on a DIN rail. Mount the DIN rail in an
enclosure or on an interior wall that meets the environmental ratings for the location (see details in
section
2.1, Enclosure
requirements).
The RMC mounting surface must have sufficient strength to support the hanging weight of the controller
(maximum of 1.816 pounds) and associated equipment to meet the requirements of IEC715. The
installation location should allow access to the RMC, power sources, cables, and connections.
If a solar panel is used, decide where and how to install the solar panel outdoors. For optimum charging,
avoid placing the solar panel where it will be in shadows any part of the day.
2.5

Wiring requirements

All wiring connections and screw terminals for power, input ports, output ports, and communications
support 12 AWG to 22 AWG. Wire gauge selection should be based on the voltage and current
requirements of the circuitry as well as the expected length of the wires. The gauge differs for each
application.
Follow local electrical codes when selecting the appropriate wire gauge and type based on the load
current, voltage, signal type, wire length, and indoor or outdoor application.
NOTICE – Equipment damage. Field installation cable and conductors must be rated
greater than 70 °C when installed in an ambient temperature greater than 60 °C.
3

Unpack and inspect

IMPORTANT NOTE: If there is any damage to the shipping carton, keep it and the packing
materials until the contents are inspected and found to be free of damage.
To unpack the RMC and inspect for damaged, missing or incorrect parts:
1.
Inspect the shipping carton for damage.
2.
Carefully remove items from the carton.
3.
Keep all shipping materials to return any parts.
4.
Compare the packing list with the materials received. Check for missing or incorrect parts.
5.
Inspect the items for damage:
 RMC exterior
 LCD display
 Optional equipment if purchased
6.
If there are any missing, incorrect, or damaged parts or noticeable defects, call the ABB main
office number listed on the last page of this guide.
4

Basic hardware installation

This is an overview of basic hardware installation. For different installations, refer to the RMC user
manual or call the ABB main office number listed on the last page of this guide.
NOTICE – Equipment damage. Perform all procedures in the order presented in this section
before powering the RMC.
DANGER – Serious damage to health / risk to life. Allowing the RMC components to
make contact with a non-insulated tool or without a proper grounding device could create a
static electric discharge resulting in bodily injury and damage to the electronic components.
Use properly insulated tools and wear a grounding strap to eliminate static electricity when
connecting or disconnecting wires.
10 | RM C-100 | 2105551MN AD

Advertisement

Table of Contents
loading

Table of Contents